FLOWHOOD CFM-88L

BACKPRESSURE COMPENSATED AIR BALANCE SYSTEM

DIRECT DIGITAL READOUT IN ENGLISH AND METRIC UNITS
AIR FLOW: Measured in cubic feet per minute (cfm) and litres per second (L/s) corrected for local air density. The measurement range is 25-2500 cfm supply and 25-1500 cfm exhaust. Accuracy is ±3% of reading ±7 cfm from 100 to 2000 cfm.
AIR DENSITY CORRECTION: The air density correction range is 14-40 in Hg and 32℉ to 158℉ for correction of air flow measurements. The readings represent local density airflow corrected for the density effects of temperature and absolute pressure.
RESPONSE TIME: Five seconds for air flows greater than 180 cfm, and up to eight seconds at less than 70 cfm.
POSITION SENSITIVITY: Unaffected by position.
READOUT: 10 digit, 0.4", high contrast, liquid crystal display.
WEIGHT: FlowHood unit with meter and 24"x24" (2'x2') top, 9.7 lbs.
UNIT DIMENSIONS: Height 40"; top 24"x24"; base 14"x14".
BATTERY LIFE: 3000 hours per charge, 500 recharge cycles.

ALSO AVAILABLE AS THE CFM-850L

UPGRADE LATER
The CFM-8L8 meter may be converted at any time into any of the multifunction "ADM" Series AirData Multimeters.